okonite wire and cable - single conductor in air
Ampacity Tables
Single Conductor In Air

Okonite Product Catalog

Engineering Technical Center
Okonite Home Page
Contact Okonite


Ask The Experts.

 

Single conductor cable in air

Single conductor cable
in air

Open circuited shield operation, i.e. shields bonded and grounded at one point only.

Air ambient temperature is 40C. Any load factor from 30 to 100%.

The ampacities are for a single, loaded cable in still air. In a group of loaded cables in close proximity in air, exposed or enclosed, follow the correction method shown on the ampacity correction factors page.

 

One cable per support or messenger

Copper

Conductor
Size
AWG-kcmil

Non-Shielded

Shielded

600-5000
Volts Ampacity

2001-5000
Volts Ampacity

5001-15,000
Volts Ampacity

15,001-35,000
Volts Ampacity

90 C
(194F)

90 C
(194F)

105C
(221F)

90 C
(194F)

105C
(221F)

90 C
(194F)

105C
(221F)

8.........
6
.........
4
.........
2
.........
1
.........
1/0
.........
2/0
.........
3/0
.........
4/0
.........
250
.........
350
.........
500
.........
750
.........
1000.........
1250.........
1500.........
1750.........
2000.........

83.........
109
.........
145
.........
192
.........
223
.........
258
.........
298
.........
345
.........
400
.........
445
.........
552
.........
695
.........
898
.........
1076
.........
1228
.........
1367
.........
1493
.........
1606
.........

83...
110
...
145
...
190
...
225
...
260
...
300
...
345
...
400
...
445
...
550
...
695
...
900
...
1075
...
1230
...
1365
...
1495
...
1605
...

93...
120
...
160
...
215
...
250
...
290
...
330
...
385
...
445
...
495
...
615
...
775
...
1000
...
1200
...
1370
...
1525
...
1665
...
1790
...

...
110
...
150
...
195
...
225
...
260
...
300
...
345
...
400
...
445
...
550
...
685
...
885
...
1060
...
1210
...
1345
...
1470
...
1575
...

...
125
...
165
...
215
...
250
...
290
...
335
...
385
...
445
...
495
...
610
...
765
...
990
...
1185
...
1350
...
1500
...
1640
...
1755
...

...
...
...
...
225
...
260
...
300
...
345
...
395
...
440
...
545
...
680
...
870
...
1040
...
1185
...
1315
...
1430
...
1535
...

...
...
...
...
250
...
290
...
330
...
380
...
445
...
490
...
605
...
755
...
970
...
1160
...
1320
...
1465
...
1595
...
1710
...

Aluminum

Conductor
Size
AWG-kcmil

Non-Shielded

Shielded

600-5000
Volts Ampacity

2001-5000
Volts Ampacity

5001-15,000
Volts Ampacity

15,001-35,000
Volts Ampacity

90 C
(194F)

90 C
(194F)

105C
(221F)

90 C
(194F)

105C
(221F)

90 C
(194F)

105C
(221F)

8.........
6
.........
4
.........
2
.........
1
.........
1/0
.........
2/0
.........
3/0
.........
4/0
.........
250
.........
350
.........
500
.........
750
.........
1000.........
1250.........
1500.........
1750.........
2000.........

64.........
85
.........
113
.........
150
.........
174
.........
201
.........
232
.........
269
.........
312
.........
347
.........
431
.........
544
.........
707
.........
853
.........
982
.........
1103
.........
1216
.........
1321
.........

64...
85
...
115
...
150
...
175
...
200
...
230
...
270
...
310
...
345
...
430
...
545
...
710
...
855
...
980
...
1105
...
1215
...
1320
...

71...
95
...
125
...
165
...
195
...
225
...
260
...
300
...
350
...
385
...
480
...
605
...
790
...
950
...
1095
...
1230
...
1355
...
1475
...

...
87
...
115
...
150
...
175
...
200
...
235
...
270
...
310
...
345
...
430
...
535
...
700
...
840
...
970
...
1085
...
1195
...
1295
...

...
97
...
130
...
170
...
195
...
225
...
260
...
300
...
350
...
385
...
480
...
600
...
780
...
940
...
1080
...
1215
...
1335
...
1445
...

...
...
...
...
175
...
200
...
230
...
270
...
310
...
345
...
430
...
530
...
685
...
825
...
950
...
1060
...
1165
...
1265
...

...
...
...
...
195
...
225
...
260
...
300
...
345
...
380
...
475
...
590
...
765
...
920
...
1055
...
1180
...
1300
...
1410
...

 


ENGINEERING TECHNICAL CENTER

Every effort has been made to ensure the accuracy of this presentation.
However, information is subject to change. Not responsible for typographical errors.

The Okonite Company
102 Hilltop Road
Ramsey, New Jersey 07446
Phone 201-825-0300
Fax 201-825-3524
info@okonite.com

Made In the USA